How many amps can 12 AWG wire carry?
25 A — copper at 75 °C, NEC Table 310.16.
12 AWG copper carries 25 A at 75 °C, 20 A at 60 °C and 30 A at 90 °C under NEC Table 310.16, before derating. NEC 240.4(D) then caps the breaker at 20 A, so 20 A is the usable answer. Aluminum at the same size is 20 A at 75 °C.
Safety first. These figures are an educational reference before derating, not a code substitute. Verify against the current NEC and have circuits reviewed by a licensed electrician.
12 AWG ampacity — copper vs aluminum
| Material | 60 °C | 75 °C | 90 °C | Breaker cap |
|---|---|---|---|---|
| Copper | 20 A | 25 A | 30 A | 20 A |
| Aluminum | 15 A | 20 A | 25 A | 15 A |
Values are amps at a 30 °C ambient, before derating for temperature or conductor bundling. Most installations must use the 75 °C column regardless of the wire's own rating, because terminals and breakers are rated 75 °C (NEC 110.14(C)).
How far can you run 12 AWG at 20 A?
Ampacity answers whether a conductor will overheat. It says nothing about whether the voltage still arrives at the far end. Past roughly fifty feet, voltage drop is usually what really sets the wire size. These are the longest one-way runs that keep drop within the 3% recommended by the NEC 210.19(A) informational note, for 12 AWG copper carrying 20 A.
| System | Typical use | Max run at 3% | Drop at 100 ft |
|---|---|---|---|
| 120 V | standard receptacle and lighting circuits | 57 ft | 6.35 V |
| 240 V | ranges, dryers, EV chargers, feeders | 113 ft | 6.35 V |
| 12 V DC | automotive, marine, solar and battery runs | 6 ft | 6.35 V |
Single-phase, one-way distance, copper at 20 °C. Aluminum reaches its limit at roughly 60% of these distances for the same size. The 3% figure is a recommendation in an informational note, not a code requirement.
12 AWG wire size — diameter, area and resistance
Diameter
0.0808 in · 2.053 mm
Cross-section
3.309 mm² · 6,530 cmil
Nearest metric size
4 mm² (rounds up)
Copper resistance
1.5882 Ω per 1000 ft @ 20 °C
Aluminum resistance
2.6523 Ω per 1000 ft
Area
6.53 kcmil
Diameter is computed from the ASTM B258 definition d = 0.005 × 92^((36 − n)/39), not read from a rounded table. Resistance uses the annealed-copper constant 10.371 Ω·cmil/ft at 20 °C.
What 12 AWG wire is used for
- 20 A circuits
- kitchen and bathroom receptacles
- garage and workshop outlets
The 12 gauge mistake worth knowing
12 AWG copper is 25 A at 75 °C, yet it is universally a 20 A wire — 240.4(D) caps the breaker at 20 A. The gap between the ampacity table and the breaker cap is why “12 gauge = 20 amps” is right even though the chart says 25.