What size wire for 80 amps?

4 AWG copper — at 75 °C terminals, NEC Table 310.16. Aluminum: 2 AWG.

A 80 A circuit needs 4 AWG copper, rated 85 A at 75 °C. If the run is NM-B (Romex), NEC 334.80 forces the 60 °C column and the answer becomes 3 AWG.

Safety first. This is a starting point before derating, not a load calculation. Wire sizing affects fire and shock safety — verify against the current NEC and have circuits designed or reviewed by a licensed electrician for your jurisdiction.

80 amp wire size by material and terminal rating

Minimum conductor size for a 80 amp circuit by material and terminal temperature rating.
Material 60 °C (NM-B) 75 °C (typical) 90 °C
copper 3 AWG (85 A) 4 AWG (85 A) 4 AWG (95 A)
aluminum 1 AWG (85 A) 2 AWG (90 A) 3 AWG (85 A)

Sizes are the smallest conductor whose ampacity and NEC 240.4(D) breaker cap both reach 80 A, before any derating. Use the 75 °C column unless every terminal, breaker and device in the circuit is rated otherwise (NEC 110.14(C)).

If the load runs continuously

A load operating for three hours or more is a continuous load, and NEC 210.19(A)(1) requires the conductor to be sized at 125% of it — 80 A becomes 100 A for sizing purposes. That moves this circuit to 3 AWG copper , one or more sizes above the 4 AWG the plain table suggests. EV chargers, electric heat and commercial lighting are the loads this catches most often.

How far can a 80 amp circuit run?

The table above only prevents overheating. On a long run the limit is voltage arriving at the far end, and it bites well before ampacity does. These are the longest one-way runs for 4 AWG copper at 80 A within the 3% drop recommended by the NEC 210.19(A) informational note — and what going up to 3 AWG buys you.

Maximum one-way run length for a 80 amp circuit by system voltage and conductor size.
System Typical use 4 AWG 3 AWG
120 V standard receptacle and lighting circuits 91 ft 114 ft
240 V ranges, dryers, EV chargers, feeders 181 ft 228 ft
12 V DC automotive, marine, solar and battery runs 9 ft 11 ft

Single-phase, one-way distance, copper at 20 °C. Aluminum reaches its limit at roughly 60% of these distances. The 3% target is a recommendation, not a code requirement.

What runs on a 80 amp circuit

The catch at 80 amps

80 A copper is 4 AWG at 75 °C (85 A). Aluminum at 80 A needs 2 AWG (90 A) — a full two sizes larger, which is why aluminum feeders always look oversized next to a copper chart.

Working the other way round? See how many amps 4 AWG carries , including its diameter, resistance and full run-length table.