How many amps can 18 AWG wire carry?

7 A — maximum overcurrent device, NEC 240.4(D).

18 AWG copper is listed at 14 A in the 90 °C column of NEC Table 310.16, but you cannot protect it at that current: NEC 240.4(D) caps the overcurrent device at 7 A, and a continuous load at 5.6 A. It is a fixture wire, not a branch-circuit conductor.

Safety first. These figures are an educational reference before derating, not a code substitute. Verify against the current NEC and have circuits reviewed by a licensed electrician.

18 AWG ampacity — copper vs aluminum

18 AWG ampacity by conductor material and insulation temperature rating.
Material 60 °C 75 °C 90 °C Breaker cap
Copper 14 A 7 A
Aluminum not rated not rated not rated

Values are amps at a 30 °C ambient, before derating for temperature or conductor bundling. Most installations must use the 75 °C column regardless of the wire's own rating, because terminals and breakers are rated 75 °C (NEC 110.14(C)).

Why the three numbers disagree. Table 310.16 lists 18 AWG copper only in the 90 °C column (14 A), because it is a fixture wire rather than a general branch-circuit conductor. NEC 240.4(D) then limits its overcurrent device to 7 A, and a load running three hours or more to 5.6 A. The 14 A figure describes the wire; the 7 A figure describes the circuit you are allowed to build with it.

How far can you run 18 AWG at 7 A?

Ampacity answers whether a conductor will overheat. It says nothing about whether the voltage still arrives at the far end. Past roughly fifty feet, voltage drop is usually what really sets the wire size. These are the longest one-way runs that keep drop within the 3% recommended by the NEC 210.19(A) informational note, for 18 AWG copper carrying 7 A.

Maximum one-way run length for 18 AWG copper at 7 A by system voltage.
System Typical use Max run at 3% Drop at 100 ft
120 V standard receptacle and lighting circuits 40 ft 8.94 V
240 V ranges, dryers, EV chargers, feeders 81 ft 8.94 V
12 V DC automotive, marine, solar and battery runs 4 ft 8.94 V

Single-phase, one-way distance, copper at 20 °C. Aluminum reaches its limit at roughly 60% of these distances for the same size. The 3% figure is a recommendation in an informational note, not a code requirement.

18 AWG wire size — diameter, area and resistance

Diameter

0.0403 in · 1.024 mm

Cross-section

0.823 mm² · 1,624 cmil

Nearest metric size

0.75 mm² (rounds down)

Copper resistance

6.3849 Ω per 1000 ft @ 20 °C

Aluminum resistance

10.6628 Ω per 1000 ft

Area

1.624 kcmil

Diameter is computed from the ASTM B258 definition d = 0.005 × 92^((36 − n)/39), not read from a rounded table. Resistance uses the annealed-copper constant 10.371 Ω·cmil/ft at 20 °C.

What 18 AWG wire is used for

The 18 gauge mistake worth knowing

18 AWG shows 14 A in the 90 °C column of Table 310.16, but 240.4(D) limits it to a 7 A overcurrent device and 5.6 A continuous. It is a fixture wire, not a branch-circuit conductor — the table value describes the wire, not the circuit you may build with it.