What size wire for 70 amps?

4 AWG copper — at 75 °C terminals, NEC Table 310.16. Aluminum: 3 AWG.

A 70 A circuit needs 4 AWG copper, rated 85 A at 75 °C. NM-B cable at the 60 °C column gives the same answer.

Safety first. This is a starting point before derating, not a load calculation. Wire sizing affects fire and shock safety — verify against the current NEC and have circuits designed or reviewed by a licensed electrician for your jurisdiction.

70 amp wire size by material and terminal rating

Minimum conductor size for a 70 amp circuit by material and terminal temperature rating.
Material 60 °C (NM-B) 75 °C (typical) 90 °C
copper 4 AWG (70 A) 4 AWG (85 A) 6 AWG (75 A)
aluminum 2 AWG (75 A) 3 AWG (75 A) 4 AWG (75 A)

Sizes are the smallest conductor whose ampacity and NEC 240.4(D) breaker cap both reach 70 A, before any derating. Use the 75 °C column unless every terminal, breaker and device in the circuit is rated otherwise (NEC 110.14(C)).

If the load runs continuously

A load operating for three hours or more is a continuous load, and NEC 210.19(A)(1) requires the conductor to be sized at 125% of it — 70 A becomes 87.5 A for sizing purposes. That moves this circuit to 3 AWG copper , one or more sizes above the 4 AWG the plain table suggests. EV chargers, electric heat and commercial lighting are the loads this catches most often.

How far can a 70 amp circuit run?

The table above only prevents overheating. On a long run the limit is voltage arriving at the far end, and it bites well before ampacity does. These are the longest one-way runs for 4 AWG copper at 70 A within the 3% drop recommended by the NEC 210.19(A) informational note — and what going up to 3 AWG buys you.

Maximum one-way run length for a 70 amp circuit by system voltage and conductor size.
System Typical use 4 AWG 3 AWG
120 V standard receptacle and lighting circuits 103 ft 131 ft
240 V ranges, dryers, EV chargers, feeders 207 ft 261 ft
12 V DC automotive, marine, solar and battery runs 10 ft 13 ft

Single-phase, one-way distance, copper at 20 °C. Aluminum reaches its limit at roughly 60% of these distances. The 3% target is a recommendation, not a code requirement.

What runs on a 70 amp circuit

The catch at 70 amps

70 A is the size where a strict ampacity reading and the Code disagree. 6 AWG copper tops out at 65 A, so a chart says 4 AWG — but 65 A is not a standard breaker rating, and NEC 240.4(B) permits rounding up to the next standard size (70 A) on a feeder that does not supply receptacles for portable loads. Both answers can be correct; which one applies depends on what the circuit feeds.

Working the other way round? See how many amps 4 AWG carries , including its diameter, resistance and full run-length table.