What size wire for 60 amps?
6 AWG copper — at 75 °C terminals, NEC Table 310.16. Aluminum: 4 AWG.
A 60 A circuit needs 6 AWG copper, rated 65 A at 75 °C. If the run is NM-B (Romex), NEC 334.80 forces the 60 °C column and the answer becomes 4 AWG.
Safety first. This is a starting point before derating, not a load calculation. Wire sizing affects fire and shock safety — verify against the current NEC and have circuits designed or reviewed by a licensed electrician for your jurisdiction.
60 amp wire size by material and terminal rating
| Material | 60 °C (NM-B) | 75 °C (typical) | 90 °C |
|---|---|---|---|
| copper | 4 AWG (70 A) | 6 AWG (65 A) | 6 AWG (75 A) |
| aluminum | 3 AWG (65 A) | 4 AWG (65 A) | 4 AWG (75 A) |
Sizes are the smallest conductor whose ampacity and NEC 240.4(D) breaker cap both reach 60 A, before any derating. Use the 75 °C column unless every terminal, breaker and device in the circuit is rated otherwise (NEC 110.14(C)).
If the load runs continuously
A load operating for three hours or more is a continuous load, and NEC 210.19(A)(1) requires the conductor to be sized at 125% of it — 60 A becomes 75 A for sizing purposes. That moves this circuit to 4 AWG copper , one or more sizes above the 6 AWG the plain table suggests. EV chargers, electric heat and commercial lighting are the loads this catches most often.
How far can a 60 amp circuit run?
The table above only prevents overheating. On a long run the limit is voltage arriving at the far end, and it bites well before ampacity does. These are the longest one-way runs for 6 AWG copper at 60 A within the 3% drop recommended by the NEC 210.19(A) informational note — and what going up to 4 AWG buys you.
| System | Typical use | 6 AWG | 4 AWG |
|---|---|---|---|
| 120 V | standard receptacle and lighting circuits | 76 ft | 121 ft |
| 240 V | ranges, dryers, EV chargers, feeders | 152 ft | 241 ft |
| 12 V DC | automotive, marine, solar and battery runs | 8 ft | 12 ft |
Single-phase, one-way distance, copper at 20 °C. Aluminum reaches its limit at roughly 60% of these distances. The 3% target is a recommendation, not a code requirement.
What runs on a 60 amp circuit
- subpanels
- large hot tubs
- electric furnaces
- commercial kitchen equipment
The catch at 60 amps
60 A sits between 6 AWG (65 A) and 4 AWG copper. 6 AWG is legal at 75 °C terminals, but a 60 A feeder to a detached structure often runs long enough that voltage drop, not ampacity, forces 4 AWG.
Working the other way round? See how many amps 6 AWG carries , including its diameter, resistance and full run-length table.