How many amps can 2 AWG wire carry?
115 A — copper at 75 °C, NEC Table 310.16.
2 AWG copper carries 115 A at 75 °C, 95 A at 60 °C and 130 A at 90 °C under NEC Table 310.16, before derating. Aluminum at the same size is 90 A at 75 °C.
Safety first. These figures are an educational reference before derating, not a code substitute. Verify against the current NEC and have circuits reviewed by a licensed electrician.
2 AWG ampacity — copper vs aluminum
| Material | 60 °C | 75 °C | 90 °C | Breaker cap |
|---|---|---|---|---|
| Copper | 95 A | 115 A | 130 A | — |
| Aluminum | 75 A | 90 A | 100 A | — |
Values are amps at a 30 °C ambient, before derating for temperature or conductor bundling. Most installations must use the 75 °C column regardless of the wire's own rating, because terminals and breakers are rated 75 °C (NEC 110.14(C)).
How far can you run 2 AWG at 115 A?
Ampacity answers whether a conductor will overheat. It says nothing about whether the voltage still arrives at the far end. Past roughly fifty feet, voltage drop is usually what really sets the wire size. These are the longest one-way runs that keep drop within the 3% recommended by the NEC 210.19(A) informational note, for 2 AWG copper carrying 115 A.
| System | Typical use | Max run at 3% | Drop at 100 ft |
|---|---|---|---|
| 120 V | standard receptacle and lighting circuits | 100 ft | 3.59 V |
| 240 V | ranges, dryers, EV chargers, feeders | 200 ft | 3.59 V |
| 12 V DC | automotive, marine, solar and battery runs | 10 ft | 3.59 V |
Single-phase, one-way distance, copper at 20 °C. Aluminum reaches its limit at roughly 60% of these distances for the same size. The 3% figure is a recommendation in an informational note, not a code requirement.
2 AWG wire size — diameter, area and resistance
Diameter
0.2576 in · 6.544 mm
Cross-section
33.631 mm² · 66,371 cmil
Nearest metric size
35 mm² (rounds up)
Copper resistance
0.1563 Ω per 1000 ft @ 20 °C
Aluminum resistance
0.2609 Ω per 1000 ft
Area
66.371 kcmil
Diameter is computed from the ASTM B258 definition d = 0.005 × 92^((36 − n)/39), not read from a rounded table. Resistance uses the annealed-copper constant 10.371 Ω·cmil/ft at 20 °C.
What 2 AWG wire is used for
- 100–115 A subpanel feeders
- service entrance
- large A/C and heat-pump circuits
The 2 gauge mistake worth knowing
“#2 copper wire ampacity” is 115 A at 75 °C — but 2 AWG aluminum is only 90 A, and mobile-home and rural feeders frequently use aluminum. Reading the copper row for an aluminum run overstates capacity by roughly a quarter.